106 changes: 106 additions & 0 deletions .claude/skills/axo-to-tco-migration/SKILL.md
Original file line number Diff line number Diff line change
@@ -0,0 +1,106 @@
---
name: axo-to-tco-migration
description: Port (migrate) an AxOpen / AX# vendor component (Axo<Device>, Simatic AX `src/components.<vendor>.<domain>`) into a TcOpen vendor component (Tco<Vendor><Domain> library, TwinCAT 3). Use when the user wants to migrate, port, convert or take over a component from AxOpen / AXOpen / AX# into this repo, or names an `Axo<Device>` class as the source. Builds on the tco-vendor-component skill.
---

# AxOpen -> TcOpen component migration

Source: the AxOpen repository, default `d:\MTS\Develop\Inxton\ax\axopen-templates\axopen` (ask if it is not there).
**The AxOpen repository is read-only.** Never edit, build, format, `apax install` or create files in it; copy files *out* of it only.

Target: a TcOpen vendor component built exactly as described by the **`tco-vendor-component`** skill. Load that skill
first - its scaffold, registration, naming, localization, testing rules and Definition of done apply unchanged. This skill
only adds how to read the AX source and how to translate AX constructs: [references/ax-to-tco-mapping.md](references/ax-to-tco-mapping.md).

## Placeholder names

This skill uses one generic name family, aligned with tco-vendor-component. Replace it consistently with the real names.

| AX placeholder | TcOpen placeholder |
|---|---|
| `components.<vendor>.<domain>` | library `Tco<Vendor><Domain>` = `TcoTemplate` |
| `AxoTemplate` (class in the `<v_X_Y_x>` namespace) | `TcoTemplate[Pn\|Ecat]_v_1_x_x` |
| `AxoTemplate_<Type>` | `TcoTemplate_<Type>_v_1_x_x` (DUTs, tasks, functions) |
| `eAxoTemplate_<Enum>` | `eTcoTemplate_<Enum>_v_1_x_x` |
| `AxoTemplate_BaseTask` | `TcoTemplateTask_v_1_x_x` (ABSTRACT) |
| `FakeTemplate` harness (`ctrl/test/_harness/`) | `TcoTemplateSimulator` in the test PLC |

Real examples are listed only at the end ([Examples](#examples-reference-ports)).

## AX library anatomy

```
src/components.<vendor>.<domain>/
ctrl/src/AxoTemplate/<v_X_Y_x>/ # component CLASS, Tasks/, TypesStructuresAndEnums/ (or flat)
ctrl/test/ # AxUnit tests, _harness/ (FakeTemplate simulator, S7Harness mocks)
ctrl/assets/ # GSDML / ESI / .hwl.yml hardware templates
src/AXOpen.Components.<Vendor>.<Domain>/ # C# twin partials: messenger text lists (code -> text + help)
Resources/PlcStringResources*.resx # translations of every <#...#> PLC text
src/AXOpen.Components.<Vendor>.<Domain>.blazor/ # views (what the operator sees) + Resources/Strings*.resx
tests/AXOpen.Components.<Vendor>.<Domain>.Tests/ # xUnit (usually messenger completeness)
docs/ # device docs, wiring, device settings, TROUBLES.md
```

A usage example usually exists in `src/showcase/app/src/components.<vendor>.<domain>/`.

## Names

- No namespaces in TwinCAT: vendor, version and (when both buses exist) bus go into every name - see the placeholder table.
- Keep the AX version folder as the version suffix (`v_X_Y_x` -> `_v_X_Y_x`).
- Keep enum member names and values exactly.

## Workflow

0. **Locate and read everything** of the component (all `.st` in `ctrl/src` and `ctrl/test`, the twin `.cs`, the
blazor view, `docs/`, assets). Use an Explore agent for a large component. Produce an inventory:
classes and members, every task's step ladder, the IO byte/bit map with offsets, every messenger code with text + help,
tests, simulator knobs, hardware template (module/slot shape).
1. **Grill** (tco-vendor-component Step 0, plus): bus (`Pn`/`Ecat`); library/FB names; which AX features to drop
(hardware-ID bootstrap, numeric codes, TaskTimeout are dropped by default - see mapping); whether AX steps are ported 1:1
(default yes, comment each block `// AX step N`). The interface map is the AX encode/decode code - no manual needed,
but read the AX docs for unverified bits and keep those notes.
2. **Check the AX code before copying it.** AX components have had real bugs (e.g. a task that never reaches Done
because of a wrong step number, a parameter stored but never used). Port the intent, tell the user about each
deviation, record it in the README.
3. **Build** with tco-vendor-component: scaffold, register, IO, DUTs, functions, task base, tasks, component, twin, view.
Translate with the mapping reference.
4. **Tests**: port the AX `FakeTemplate` harness into `TcoTemplateSimulator` (same knobs: fail/silent/stuck masks,
timing counts, fault flags) and port each AxUnit test into an NUnit PLC-executed test. Tests of the AX hardware
bootstrap (`S7Harness`, HW-ID codes) are dropped together with that feature. Codec tests become mapping tests
(write raw bytes into the simulated input image, assert the decoded `_status`; set `_control`, assert output bytes).
5. **Localization**: neutral texts come from the PLC `<#...#>` literals. AX `PlcStringResources.<de|es|sk>.resx` and blazor
`Strings.*.resx` are a translation source when the English text is the same - reuse their wording, then fill the gaps
(cs-CZ never exists in AX). AX help texts (C# messenger list) are merged into the TcOpen message text where useful.
6. **README**: wiring, hardware template/slot table, device settings, byte maps, troubleshooting - from AX `docs/`.
Copy GSDML/ESI from `ctrl/assets` to `assets/` and `TcoTemplateConnector/ddf/`.
7. **Report** to the user: what was dropped, AX bugs fixed, tests that could not be run.

## Verification without TwinCAT XAE

- **Library twin**: write a temporary filter in the repo root (`TcoTemplate.tmp.slnf`, `"path": "TcOpen.sln"`) with the
library Connector, the Xae tsproj and the TestsConnector, then
`.\_Vortex\builder\vortex.compiler.console.exe -s .\TcoTemplate.tmp.slnf -n false`. It parses the PLC declarations and
regenerates `_generated/`; `WRN ... unknown type` on library types means a misspelt name. Delete the filter afterwards.
- **Test PLC twin**: the compiler resolves types of *referenced PLC libraries* from the TwinCAT managed library repository
(`C:\TwinCAT\3.1\Components\Plc\Managed Libraries\Vortex.Library\TcoTemplate`). A brand-new library is not there until
it is built and installed from XAE, so the test-connector twin (and the NUnit project) only compile after that - say so.
- **.NET**: the connector packs `_meta\TcoTemplate.library`, which only an XAE build produces. To check that the C#
compiles earlier, put an empty placeholder file there for the build and delete it afterwards (`_meta/` is gitignored).
- ST implementation bodies are not checked by the Vortex compiler - review them, and build in XAE before release.
- In this environment bash heredocs collapse `\\`; write JSON (`.slnf`) with the Write tool or a script file.

## Extra definition-of-done items

- [ ] Nothing written to the AxOpen repository (`git -C <axopen> status` clean).
- [ ] Every AX task, operation and public data member is either ported or listed as dropped in the README.
- [ ] No AX identifiers or syntax left in the TcOpen code: `Axo*` types, `ix-attr`, `ix-set`, `REF_TO`, `LTIME`, `THIS.` (case-sensitive search; doc comments naming the AX origin are fine, and words like `RealTime` / `MaxOutputs` are false hits of a case-insensitive search).
- [ ] Every AX test is ported or listed as not applicable.

## Examples (reference ports)

Read them when a detail is unclear. Do not copy vendor names, signal names or texts from them into a new component.

| AX source | TcOpen port | What it shows |
|---|---|---|
| `components.ateq.measurement`, `AxoG6` `v_3_5_x` | `src/TcoAteqMeasurement`, `TcoAteqG6Pn_v_3_5_x` | cyclic PN with 4+4 modules mapped to one image, command handshake in an abstract task base, AX data classes as STRUCT + FUNCTIONs, simulator ported from `FakeG6`, numeric codes replaced by texts |
| `components.kuka.robotics`, `AxoKss` `v_9_3_x` | `src/TcoKukaRobotics`, `TcoKukaKssPn_v_9_3_x` / `...Ecat...` | 1:1 step port with `// AX step N`, both buses, AX bug fixed (start task never reached Done) |
108 changes: 108 additions & 0 deletions .claude/skills/axo-to-tco-migration/references/ax-to-tco-mapping.md
Original file line number Diff line number Diff line change
@@ -0,0 +1,108 @@
# AX -> TcOpen translation table

Derived from the reference ports listed in SKILL.md (Examples).
Names use the placeholder families of SKILL.md: `AxoTemplate` (AX) and `TcoTemplate` (TcOpen).

## Component

| AX | TcOpen |
|---|---|
| `CLASS AxoTemplate EXTENDS AXOpen.Core.AxoComponent` | `FUNCTION_BLOCK TcoTemplatePn_v_1_x_x EXTENDS TcoIo.TcoPnIoComponent` (`TcoIo.TcoEcatComponent`, `TcoCore.TcoComponent` for .NET TCP) |
| `IMPLEMENTS IAxo<Abstraction>` (e.g. `IAxoRobotics`) | `IMPLEMENTS TcoAbstractions.ITco<Abstraction>`; reuse the `TcoAbstractions` types instead of the AX ones |
| `METHOD PUBLIC Run(inParent : IAxoObject; hwID : UINT)` | FB body with `VAR_IN_OUT inoData : TcoTemplate_IO_v_1_x_x`; parent bound at declaration `(THIS^)` + `FB_init(bInitRetains, bInCopyCode, ParentObject : ITcoObject)` |
| `SUPER.Run(inParent); Messenger.Serve(THIS);` | `IF NOT __ISVALIDREF(inoData) ...RETURN; SUPER^(inPnIoBoxState := ..., inPnIoBoxDiag := ...); _busError := NOT _profinetReady;` |
| `InitHwCheck` / `CheckSubmodule` (`ReadSlotFromHardwareID`, `ReadHardwareIDFromSlot`, `ReadHardwareIOAddress`, size checks) | **dropped** - IO is linked in the System Manager; module sizes are fixed by the IO struct |
| `Config.HWIDs`, `AxoTemplate_HWIDs` | **dropped** |
| `DistributedIO.ReadData(hwID, _module)` per module | one `ARRAY[0..n] OF BYTE AT %I*` per module in `TcoTemplate_Inputs_v_1_x_x` (`In1..InN`, one per module), copied into an image with `MEMCPY` in `UpdateStatus` |
| `DistributedIO.WriteData` | `Out1..OutN AT %Q*` in `_Outputs_`, filled in `UpdateControl` (last statement of the body) |
| `HardwareDiagnosticsTask : AxoHardwareDiagnostics` | **dropped** - PN box state / `_busError` of `TcoPnIoComponent` |
| `Inputs : AxoTemplate_State` + `Status : AxoTemplate_Component_Status` | `_status : TcoTemplate_Status_v_1_x_x` with `ActionDescription` + `State` (+ any extra AX status data) |
| `Outputs : AxoTemplate_Control` | `_control : TcoTemplate_Control_v_1_x_x` |
| public fields `Config`, `Status`, task fields | private `_camelCase` + `PROPERTY Status : REFERENCE TO ...` / `PROPERTY XTask : TcoCore.ITcoTaskStatus` |
| `METHOD ... : IAxoTaskState` | `METHOD ... : TcoCore.ITcoTaskStatus` |
| `RestoreTask.Execute(THIS)` -> `THIS.Restore()` (calls `RestoreTask.DoneWhen(TRUE)` inside) | `IF _restoreTask.Execute() THEN Restore(); _restoreTask.DoneWhen(TRUE); END_IF`; `Restore : ITcoRestorable` = `RestoreTasks()` + safe `_control` |
| `METHOD PROTECTED OVERRIDE ManualControl` | `METHOD PROTECTED ServiceMode` |
| `Status.Action.Id := 50` | `_status.ActionDescription := '<#Restore has been executed.#>'` |

## Tasks

| AX (`AxoTask`) | TcOpen (`TcoCore.TcoTask`) |
|---|---|
| `CLASS ABSTRACT AxoTemplate_BaseTask EXTENDS AxoTask` | `FUNCTION_BLOCK ABSTRACT TcoTemplateTask_v_1_x_x EXTENDS TcoCore.TcoTask` |
| `Run(parent, REF(Config), REF(Status), ...)` + `refX : REF_TO T`, NULL checks | `VAR_IN_OUT inoConfig, inoControl, inoStatus (, inoImage ...)` passed every call; step 0 = `CheckReferences()` (`__ISVALIDREF`) |
| `task.SetIsDisabled(cond); task.Run(...)` | `task.Enabled := NOT cond; task(inoConfig := ..., ...)` - **polarity inverted** |
| `IsBusy() / IsDone() / HasError() / IsReady()` | properties `Busy / Done / Error / Ready` |
| `Execute(THIS)`, `Invoke(THIS)`, `Abort()` | `Execute()`, `Invoke()`, `Abort()` |
| `DoneWhen(TRUE)` | `DoneWhen(TRUE)` |
| `ThrowWhen(cond, '<#text#>')` | `ThrowWhen(cond)` has no text: store the text in a task variable first (`Fail(inText)` helper), post it from `OnError` |
| `OnStart / OnDone / OnError / OnAbort` (OVERRIDE, `SUPER.OnX()`) | `OnStart / OnDone / OnError / OnAbort` (no SUPER call needed), each guarded by `IF __ISVALIDREF(inoStatus)` |
| `OnRestore` | override `Restore : ITcoRestorable` (`SUPER^.Restore(); ...`) |
| no auto-restore | task ends with `IF THIS^.Error AND NOT _errorMessage.Pinned THEN THIS^.Restore(); END_IF`; `OnError` pins `_errorMessage` |
| `Duration` | `ElapsedTime` (rarely needed; use timers) |
| `Config.TaskTimeout` + `ThrowWhen(Duration >= ...)` | **dropped** - `Config.ErrorTime` with `_errorTimer` / `ThrowWhen(_errorTimer.Q)` (T#0S = off) |
| `Messenger.Post(Status.ActionInfo, Info)` after `InfoTime` | `Messenger.OnCondition(_infoTimer.Q).Warning/Info(...)` |
| parameters stored on the component before `Invoke` | task-local variable + `InvokeWithParams(...)` or fluent `WithParams(...)`; or `_control` data written by the operation method (cyclic) |
| sequential `IF _progress = N THEN` | same idiom; comment each block `// AX step N` (step numbers may be kept as in AX, e.g. 0/10/20/100) |
| `GoTo(step)` restarting a step timer | `_progress := step; _stepTimer(IN := FALSE);` |
| `AxoRemoteTask` | `TcoCore.TcoRemoteTask` (.NET TCP archetype) |

## Messenger

| AX | TcOpen |
|---|---|
| `Messenger : AxoMessenger` field + `Serve(THIS)` | built-in `Messenger`; tasks add `_errorMessage : TcoCore.TcoMessenger(THIS^)` |
| `Messenger.Activate(UINT#n, Error)` + C# `MessengerTextList` (code -> text, help) | `Messenger.Error('<#text#>')` with the AX text (and help when short) inline; **numeric codes dropped** |
| `Status.Error.Id := n` | dropped (or a diagnostic field only when the user asks) |
| categories `Error / Warning / Info / ProgrammingError / Potential` | `Error / Warning / Info / Programming / Warning` |
| `ActivateOnCondition(n, cond, cat)` | `Messenger.OnCondition(cond).<Category>(...)` |
| `Messenger.Restore()` | `UnPin()` |

## Data types and language

| AX | TcOpen |
|---|---|
| `CLASS` with data + methods (Decode/Encode/Add/Clear) | `STRUCT` DUT + `FUNCTION`s `Tco<Vendor><Device>_<Verb><Type>_v_X_Y_x(VAR_IN_OUT ...)`; FB only if it must keep state between cycles |
| `CLASS` used only as data | `STRUCT` |
| `ARRAY[*] OF BYTE` parameter | fixed bounds (`ARRAY[0..255] OF BYTE`) or `POINTER TO BYTE` + size |
| `REF_TO T`, `^`, `REF(x)`, `NULL` | `VAR_IN_OUT` (preferred), `REFERENCE TO` + `REF=`, `__ISVALIDREF` |
| `THIS.` / `SUPER.` | `THIS^.` / `SUPER^.` |
| method overloads | distinct names |
| `VAR PUBLIC/PROTECTED` | FB `VAR` + properties; inherited `VAR` are visible to subclasses |
| `LTIME`, `LT#5S` | `TIME`, `T#5S` |
| `OnDelayTimer.OnDelay(THIS, sig, t)`, `.output`, `.Restore()` | `TON`: `t(IN := sig, PT := ...)`, `.Q`, `t(IN := FALSE)` |
| `AxoBlinker` | `TcoUtilities.TcoBlinker(THIS^)` (check period) |
| `TO_INT`, `TO_REAL`, `TO_WORD` | explicit `WORD_TO_INT`, `DINT_TO_REAL`, `INT_TO_WORD` ... |
| `UINT#5`, `WORD#16#8000` | plain literals with typed context (`16#8000`) |
| `STRING` (unbounded) | `STRING(n)` - `ActionDescription : STRING(100)`, texts up to 254 |
| `x.%X3`, `%B0` | `x.3`, byte helpers / `SHL` / `TcoUtilities.TcoBytesTo*` (`eTcoDataFormat.LittleEndian`) |

## Attributes

| AX | TcOpen |
|---|---|
| `{#ix-set:AttributeName = "<#X#>"}` | `{attribute addProperty Name "<#X#>"}` |
| `{#ix-attr:[ReadOnly()]}` | `{attribute clr [ReadOnly()]}` |
| `{#ix-attr:[RenderIgnore()]}` | `{attribute clr [RenderIgnore()]}` or `{attribute 'hide'}` for internals |
| `{#ix-attr:[ComponentDetails(...)]}`, `[Container(...)]`, `[Group(...)]`, `{S7.extern=...}` | drop - layout is the WPF view's job |
| `///<summary>` | `(*~ <docu><summary> ... </summary></docu> ~*)` |
| enum | `{attribute 'qualified_only'}` + `{attribute 'strict'}` |

## Tests and UI

| AX | TcOpen |
|---|---|
| AxUnit `{TestFixture}` / `{Test}` in `ctrl/test` | test PLC test context + NUnit `PlcExectutedTests/` (testing.md of tco-vendor-component) |
| `_harness/Fake<Device>.st` simulator | simulator section of the test context `Main`, same knobs as `_sim*` / `_fault*` variables |
| `S7Harness` (HW-ID / ReadData mocks) | none - tests write the unlinked `_io` struct directly |
| xUnit messenger-completeness tests | none (codes dropped); `Test-TcoLocalization.ps1` checks the texts instead |
| Blazor view + tabs | WPF `<Gen>/Service/<FB>ServiceView.xaml` + view model (status badges, values, task buttons, data panels) |

## Gotchas

- `Enabled` is the inverse of `SetIsDisabled`; re-read each interlock line.
- Several AX `IF _progress = N` blocks may advance within one cycle - the TcOpen idiom does the same; keep block order.
- AX step numbering: TcOpen adds `CheckReferences`; either insert it as an extra step before AX step 0 or check references in the body before the step blocks.
- Profinet devices with several modules: one `AT %I*` array per module; keep the AX image offsets so the decode code stays 1:1.
- Numbers that are 0-based on the bus and 1-based in AX (e.g. program or recipe numbers): keep the AX conversion in the encode/decode functions.
- AX writes the whole output image every cycle (zeroed then encoded) - do the same in `UpdateControl`.
- Unaligned multi-byte fields: decode via byte helpers, not struct overlays (TwinCAT pack mode).
Loading