Skip to content

[BUG] Fix: MissedAcquisition after TriggerEnable reset in TcoDataman #48

Closed

Description

@mhareznik

Problem

After an intentional TriggerEnable FALSE → TRUE reset sequence, the function block sends a trigger too early. The TriggerReady bit seen by the PLC can be a stale PROFINET packet value — the DataMan is not yet internally ready, resulting in MissedAcquisition.

Fix

After TriggerEnable rising edge, wait for TriggerReady = TRUE stable for at least 2 consecutive PROFINET cycles (≥ 32 ms) before allowing a trigger.

Activity

  1. added
    bugSomething isn't working
    questionFurther information is requested
    on Apr 29, 2026
  2. peterbarancek commented on May 25, 2026

    @peterbarancek
    Collaborator

    /cib

  3. github-actions commented on May 25, 2026

    @github-actions
    Contributor
  4. added a commit that references this issue on May 25, 2026
Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment