225 changes: 225 additions & 0 deletions EUROTHRM/EUROTHRM-IOC-01App/Db/devEurothrm.db
Original file line number Diff line number Diff line change
Expand Up @@ -989,6 +989,175 @@ record(calc, "$(P)TEMP:RANGE:OVER") {
field(CALC, "B < A")
}

record(ai, "$(P)AUTOMAN") {
Copy link
Copy Markdown
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

This should probably be a bi as it appears to be an on/off value not an analog one

field(DESC, "Auto or Manual selected")
field(SCAN, "10 second")

$(IFUSES_BISYNCH) field(DTYP, "stream")
$(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),mA,$(GAD),$(LAD)) $(PORT)")

$(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32")
$(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),273,1000)MODBUS_DATA")
$(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)")

field(SIML, "$(Q)SIM")
field(SIOL, "$(P)SIM:AUTOMAN")
field(SDIS, "$(Q)DISABLE")
field(PREC, "3")
}

record(ao, "$(P)AUTOMAN:SP") {
Copy link
Copy Markdown
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

as above, but should be bo

field(DESC, "Auto or Manual Setpoint")

$(IFUSES_BISYNCH) field(DTYP, "stream")
$(IFUSES_BISYNCH) field(OUT, "@eurotherm2k.proto write($(P),mA,$(GAD),$(LAD)) $(PORT)")

$(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32")
$(IFNOTUSES_BISYNCH) field(OUT, "@asyn(MODBUS_TX_$(GAD)$(LAD),273,1000)MODBUS_DATA")

field(SIML, "$(Q)SIM")
field(SIOL, "$(P)SIM:AUTOMAN:SP")
field(SDIS, "$(Q)DISABLE")
field(FLNK, "$(P)AUTOMAN.PROC")
field(EGU, "")
}

record(ai, "$(P)LOWRANGE") {
field(DESC, "Low range limit")
field(SCAN, "10 second")

$(IFUSES_BISYNCH) field(DTYP, "stream")
$(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),QC,$(GAD),$(LAD)) $(PORT)")

$(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32")
$(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),11,1000)MODBUS_DATA")
$(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)")

field(SIML, "$(Q)SIM")
field(SIOL, "$(P)SIM:LOWRANGE")
field(SDIS, "$(Q)DISABLE")
field(PREC, "3")
}

record(ai, "$(P)HIRANGE") {
field(DESC, "High range limit")
field(SCAN, "10 second")

$(IFUSES_BISYNCH) field(DTYP, "stream")
$(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),QB,$(GAD),$(LAD)) $(PORT)")

$(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32")
$(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),12,1000)MODBUS_DATA")
$(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)")

field(SIML, "$(Q)SIM")
field(SIOL, "$(P)SIM:HIRANGE")
field(SDIS, "$(Q)DISABLE")
field(PREC, "3")
}

record(ai, "$(P)WORKOUTP") {
field(DESC, "Working Output")
field(SCAN, "10 second")

$(IFUSES_BISYNCH) field(DTYP, "stream")
$(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),WO,$(GAD),$(LAD)) $(PORT)")

$(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32")
$(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),4,1000)MODBUS_DATA")
$(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)")

field(SIML, "$(Q)SIM")
field(SIOL, "$(P)SIM:WORKOUTP")
field(SDIS, "$(Q)DISABLE")
field(PREC, "3")
}

record(ai, "$(P)OUTLOWLM") {
field(DESC, "Low power limit")
field(SCAN, "10 second")

$(IFUSES_BISYNCH) field(DTYP, "stream")
$(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),LO,$(GAD),$(LAD)) $(PORT)")

$(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32")
$(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),31,1000)MODBUS_DATA")
$(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)")

field(SIML, "$(Q)SIM")
field(SIOL, "$(P)SIM:OUTLOWLM")
field(SDIS, "$(Q)DISABLE")
field(PREC, "3")
}

record(ai, "$(P)OUTPCOMP") {
field(DESC, "Proportional component of output")
field(SCAN, "10 second")

$(IFUSES_BISYNCH) field(DTYP, "stream")
$(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),xP,$(GAD),$(LAD)) $(PORT)")

$(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32")
$(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),214,1000)MODBUS_DATA")
$(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)")

field(SIML, "$(Q)SIM")
field(SIOL, "$(P)SIM:OUTPCOMP")
field(SDIS, "$(Q)DISABLE")
field(PREC, "3")
}

record(ai, "$(P)OUTICOMP") {
field(DESC, "Integral component of output")
field(SCAN, "10 second")

$(IFUSES_BISYNCH) field(DTYP, "stream")
$(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),xI,$(GAD),$(LAD)) $(PORT)")

$(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32")
$(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),55,1000)MODBUS_DATA")
$(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)")

field(SIML, "$(Q)SIM")
field(SIOL, "$(P)SIM:OUTICOMP")
field(SDIS, "$(Q)DISABLE")
field(PREC, "3")
}

record(ai, "$(P)OUTDCOMP") {
field(DESC, "Derivative component of output")
field(SCAN, "10 second")

$(IFUSES_BISYNCH) field(DTYP, "stream")
$(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),xD,$(GAD),$(LAD)) $(PORT)")

$(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32")
$(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),55,1000)MODBUS_DATA")
$(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)")

field(SIML, "$(Q)SIM")
field(SIOL, "$(P)SIM:OUTDCOMP")
field(SDIS, "$(Q)DISABLE")
field(PREC, "3")
}

record(ai, "$(P)SNBRKPST") {
Copy link
Copy Markdown
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

This should probably be a bi as it appears to be a binary flag rather than an analog value

field(DESC, "Sensor break status flag")
field(SCAN, "10 second")

$(IFUSES_BISYNCH) field(DTYP, "stream")
$(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),sb,$(GAD),$(LAD)) $(PORT)")

$(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32")
$(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),258,1000)MODBUS_DATA")
$(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)")

field(SIML, "$(Q)SIM")
field(SIOL, "$(P)SIM:SNBRKPST")
field(SDIS, "$(Q)DISABLE")
field(PREC, "3")
}

### SIMULATION RECORDS ###

record(ai, "$(P)SIM:MAX_OUTPUT")
Expand Down Expand Up @@ -1086,3 +1255,59 @@ record(ai, "$(P)SIM:TEMP:HIGHLIMIT")
field(SCAN, "Passive")
field(DTYP, "Soft Channel")
}

record(ai, "$(P)SIM:AUTOMAN")
Copy link
Copy Markdown
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

as non simulation, this should be bi

{
field(SCAN, "Passive")
field(DTYP, "Soft Channel")
}

alias("$(P)SIM:AUTOMAN","$(P)SIM:AUTOMAN:SP")

record(ai, "$(P)SIM:LOWRANGE")
{
field(SCAN, "Passive")
field(DTYP, "Soft Channel")
}

record(ai, "$(P)SIM:HIRANGE")
{
field(SCAN, "Passive")
field(DTYP, "Soft Channel")
}

record(ai, "$(P)SIM:WORKOUTP")
{
field(SCAN, "Passive")
field(DTYP, "Soft Channel")
}

record(ai, "$(P)SIM:OUTLOWLM")
{
field(SCAN, "Passive")
field(DTYP, "Soft Channel")
}

record(ai, "$(P)SIM:OUTPCOMP")
{
field(SCAN, "Passive")
field(DTYP, "Soft Channel")
}

record(ai, "$(P)SIM:OUTICOMP")
{
field(SCAN, "Passive")
field(DTYP, "Soft Channel")
}

record(ai, "$(P)SIM:OUTDCOMP")
{
field(SCAN, "Passive")
field(DTYP, "Soft Channel")
}

record(ai, "$(P)SIM:SNBRKPST")
Copy link
Copy Markdown
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

as non simulation, this should be bi

{
field(SCAN, "Passive")
field(DTYP, "Soft Channel")
}