Notifications
You must be signed in to change notification settings - Fork 1
Ticket8688 add attributes to eurotherm #950
New issue
Have a question about this project? Sign up for a free GitHub account to open an issue and contact its maintainers and the community.
By clicking “Sign up for GitHub”, you agree to our terms of service and privacy statement. We’ll occasionally send you account related emails.
Already on GitHub? Sign in to your account
base: master
Are you sure you want to change the base?
Changes from all commits
File filter
Filter by extension
Conversations
Jump to
Diff view
Diff view
There are no files selected for viewing
| Original file line number | Diff line number | Diff line change |
|---|---|---|
|
|
@@ -989,6 +989,175 @@ record(calc, "$(P)TEMP:RANGE:OVER") { | |
| field(CALC, "B < A") | ||
| } | ||
|
|
||
| record(ai, "$(P)AUTOMAN") { | ||
| field(DESC, "Auto or Manual selected") | ||
| field(SCAN, "10 second") | ||
|
|
||
| $(IFUSES_BISYNCH) field(DTYP, "stream") | ||
| $(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),mA,$(GAD),$(LAD)) $(PORT)") | ||
|
|
||
| $(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32") | ||
| $(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),273,1000)MODBUS_DATA") | ||
| $(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)") | ||
|
|
||
| field(SIML, "$(Q)SIM") | ||
| field(SIOL, "$(P)SIM:AUTOMAN") | ||
| field(SDIS, "$(Q)DISABLE") | ||
| field(PREC, "3") | ||
| } | ||
|
|
||
| record(ao, "$(P)AUTOMAN:SP") { | ||
|
Contributor
There was a problem hiding this comment. Choose a reason for hiding this commentThe reason will be displayed to describe this comment to others. Learn more. as above, but should be |
||
| field(DESC, "Auto or Manual Setpoint") | ||
|
|
||
| $(IFUSES_BISYNCH) field(DTYP, "stream") | ||
| $(IFUSES_BISYNCH) field(OUT, "@eurotherm2k.proto write($(P),mA,$(GAD),$(LAD)) $(PORT)") | ||
|
|
||
| $(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32") | ||
| $(IFNOTUSES_BISYNCH) field(OUT, "@asyn(MODBUS_TX_$(GAD)$(LAD),273,1000)MODBUS_DATA") | ||
|
|
||
| field(SIML, "$(Q)SIM") | ||
| field(SIOL, "$(P)SIM:AUTOMAN:SP") | ||
| field(SDIS, "$(Q)DISABLE") | ||
| field(FLNK, "$(P)AUTOMAN.PROC") | ||
| field(EGU, "") | ||
| } | ||
|
|
||
| record(ai, "$(P)LOWRANGE") { | ||
| field(DESC, "Low range limit") | ||
| field(SCAN, "10 second") | ||
|
|
||
| $(IFUSES_BISYNCH) field(DTYP, "stream") | ||
| $(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),QC,$(GAD),$(LAD)) $(PORT)") | ||
|
|
||
| $(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32") | ||
| $(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),11,1000)MODBUS_DATA") | ||
| $(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)") | ||
|
|
||
| field(SIML, "$(Q)SIM") | ||
| field(SIOL, "$(P)SIM:LOWRANGE") | ||
| field(SDIS, "$(Q)DISABLE") | ||
| field(PREC, "3") | ||
| } | ||
|
|
||
| record(ai, "$(P)HIRANGE") { | ||
| field(DESC, "High range limit") | ||
| field(SCAN, "10 second") | ||
|
|
||
| $(IFUSES_BISYNCH) field(DTYP, "stream") | ||
| $(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),QB,$(GAD),$(LAD)) $(PORT)") | ||
|
|
||
| $(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32") | ||
| $(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),12,1000)MODBUS_DATA") | ||
| $(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)") | ||
|
|
||
| field(SIML, "$(Q)SIM") | ||
| field(SIOL, "$(P)SIM:HIRANGE") | ||
| field(SDIS, "$(Q)DISABLE") | ||
| field(PREC, "3") | ||
| } | ||
|
|
||
| record(ai, "$(P)WORKOUTP") { | ||
| field(DESC, "Working Output") | ||
| field(SCAN, "10 second") | ||
|
|
||
| $(IFUSES_BISYNCH) field(DTYP, "stream") | ||
| $(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),WO,$(GAD),$(LAD)) $(PORT)") | ||
|
|
||
| $(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32") | ||
| $(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),4,1000)MODBUS_DATA") | ||
| $(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)") | ||
|
|
||
| field(SIML, "$(Q)SIM") | ||
| field(SIOL, "$(P)SIM:WORKOUTP") | ||
| field(SDIS, "$(Q)DISABLE") | ||
| field(PREC, "3") | ||
| } | ||
|
|
||
| record(ai, "$(P)OUTLOWLM") { | ||
| field(DESC, "Low power limit") | ||
| field(SCAN, "10 second") | ||
|
|
||
| $(IFUSES_BISYNCH) field(DTYP, "stream") | ||
| $(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),LO,$(GAD),$(LAD)) $(PORT)") | ||
|
|
||
| $(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32") | ||
| $(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),31,1000)MODBUS_DATA") | ||
| $(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)") | ||
|
|
||
| field(SIML, "$(Q)SIM") | ||
| field(SIOL, "$(P)SIM:OUTLOWLM") | ||
| field(SDIS, "$(Q)DISABLE") | ||
| field(PREC, "3") | ||
| } | ||
|
|
||
| record(ai, "$(P)OUTPCOMP") { | ||
| field(DESC, "Proportional component of output") | ||
| field(SCAN, "10 second") | ||
|
|
||
| $(IFUSES_BISYNCH) field(DTYP, "stream") | ||
| $(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),xP,$(GAD),$(LAD)) $(PORT)") | ||
|
|
||
| $(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32") | ||
| $(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),214,1000)MODBUS_DATA") | ||
| $(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)") | ||
|
|
||
| field(SIML, "$(Q)SIM") | ||
| field(SIOL, "$(P)SIM:OUTPCOMP") | ||
| field(SDIS, "$(Q)DISABLE") | ||
| field(PREC, "3") | ||
| } | ||
|
|
||
| record(ai, "$(P)OUTICOMP") { | ||
| field(DESC, "Integral component of output") | ||
| field(SCAN, "10 second") | ||
|
|
||
| $(IFUSES_BISYNCH) field(DTYP, "stream") | ||
| $(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),xI,$(GAD),$(LAD)) $(PORT)") | ||
|
|
||
| $(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32") | ||
| $(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),55,1000)MODBUS_DATA") | ||
| $(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)") | ||
|
|
||
| field(SIML, "$(Q)SIM") | ||
| field(SIOL, "$(P)SIM:OUTICOMP") | ||
| field(SDIS, "$(Q)DISABLE") | ||
| field(PREC, "3") | ||
| } | ||
|
|
||
| record(ai, "$(P)OUTDCOMP") { | ||
| field(DESC, "Derivative component of output") | ||
| field(SCAN, "10 second") | ||
|
|
||
| $(IFUSES_BISYNCH) field(DTYP, "stream") | ||
| $(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),xD,$(GAD),$(LAD)) $(PORT)") | ||
|
|
||
| $(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32") | ||
| $(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),55,1000)MODBUS_DATA") | ||
| $(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)") | ||
|
|
||
| field(SIML, "$(Q)SIM") | ||
| field(SIOL, "$(P)SIM:OUTDCOMP") | ||
| field(SDIS, "$(Q)DISABLE") | ||
| field(PREC, "3") | ||
| } | ||
|
|
||
| record(ai, "$(P)SNBRKPST") { | ||
|
Contributor
There was a problem hiding this comment. Choose a reason for hiding this commentThe reason will be displayed to describe this comment to others. Learn more. This should probably be a |
||
| field(DESC, "Sensor break status flag") | ||
| field(SCAN, "10 second") | ||
|
|
||
| $(IFUSES_BISYNCH) field(DTYP, "stream") | ||
| $(IFUSES_BISYNCH) field(INP, "@eurotherm2k.proto read($(P),sb,$(GAD),$(LAD)) $(PORT)") | ||
|
|
||
| $(IFNOTUSES_BISYNCH) field(DTYP, "asynInt32") | ||
| $(IFNOTUSES_BISYNCH) field(INP, "@asyn(MODBUS_RX_$(GAD)$(LAD),258,1000)MODBUS_DATA") | ||
| $(IFNOTUSES_BISYNCH) field(ASLO, "$(TEMP_SCALING)") | ||
|
|
||
| field(SIML, "$(Q)SIM") | ||
| field(SIOL, "$(P)SIM:SNBRKPST") | ||
| field(SDIS, "$(Q)DISABLE") | ||
| field(PREC, "3") | ||
| } | ||
|
|
||
| ### SIMULATION RECORDS ### | ||
|
|
||
| record(ai, "$(P)SIM:MAX_OUTPUT") | ||
|
|
@@ -1086,3 +1255,59 @@ record(ai, "$(P)SIM:TEMP:HIGHLIMIT") | |
| field(SCAN, "Passive") | ||
| field(DTYP, "Soft Channel") | ||
| } | ||
|
|
||
| record(ai, "$(P)SIM:AUTOMAN") | ||
|
Contributor
There was a problem hiding this comment. Choose a reason for hiding this commentThe reason will be displayed to describe this comment to others. Learn more. as non simulation, this should be |
||
| { | ||
| field(SCAN, "Passive") | ||
| field(DTYP, "Soft Channel") | ||
| } | ||
|
|
||
| alias("$(P)SIM:AUTOMAN","$(P)SIM:AUTOMAN:SP") | ||
|
|
||
| record(ai, "$(P)SIM:LOWRANGE") | ||
| { | ||
| field(SCAN, "Passive") | ||
| field(DTYP, "Soft Channel") | ||
| } | ||
|
|
||
| record(ai, "$(P)SIM:HIRANGE") | ||
| { | ||
| field(SCAN, "Passive") | ||
| field(DTYP, "Soft Channel") | ||
| } | ||
|
|
||
| record(ai, "$(P)SIM:WORKOUTP") | ||
| { | ||
| field(SCAN, "Passive") | ||
| field(DTYP, "Soft Channel") | ||
| } | ||
|
|
||
| record(ai, "$(P)SIM:OUTLOWLM") | ||
| { | ||
| field(SCAN, "Passive") | ||
| field(DTYP, "Soft Channel") | ||
| } | ||
|
|
||
| record(ai, "$(P)SIM:OUTPCOMP") | ||
| { | ||
| field(SCAN, "Passive") | ||
| field(DTYP, "Soft Channel") | ||
| } | ||
|
|
||
| record(ai, "$(P)SIM:OUTICOMP") | ||
| { | ||
| field(SCAN, "Passive") | ||
| field(DTYP, "Soft Channel") | ||
| } | ||
|
|
||
| record(ai, "$(P)SIM:OUTDCOMP") | ||
| { | ||
| field(SCAN, "Passive") | ||
| field(DTYP, "Soft Channel") | ||
| } | ||
|
|
||
| record(ai, "$(P)SIM:SNBRKPST") | ||
|
Contributor
There was a problem hiding this comment. Choose a reason for hiding this commentThe reason will be displayed to describe this comment to others. Learn more. as non simulation, this should be |
||
| { | ||
| field(SCAN, "Passive") | ||
| field(DTYP, "Soft Channel") | ||
| } | ||
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
This should probably be a
bias it appears to be an on/off value not an analog one