From the C++ controller to a PLC

The existing Controller.hpp and Controller.cpp already separate control decisions from physical movement. FactoryFlow.st translates that same controller into IEC 61131-3 Structured Text (ST). It adds no simulation or control features. Read the ST file from top to bottom: data types, controller, cyclic caller.

Concept mapping

C++ concept PLC equivalent Meaning in FactoryFlow
Inputs A structure of BOOL values representing the input process image A snapshot of sensor and fault signals used for this scan.
Outputs A structure of BOOL commands representing the output process image Motor and diverter commands sent to output channels after execution.
Controller object An FB_Controller function block instance Owns sequence state across calls.
scan(inputs) One execution of the function block body Checks safety, updates state, then calculates outputs.
State and switch An enumerated type and CASE Selects one sequence branch per call.
Sensor calculations in main.cpp Physical sensors connected to digital input channels The plant supplies feedback; the controller does not calculate box position.
conveyorMotor A digital run command to a drive or motor starter Requests motion; it is not motor power or a speed setpoint.
diverterA/B/C Digital commands to diverter actuators, such as valve solenoids Only B is selected in this milestone. Commands are not arrival feedback.
The approximately 10 ms C++ loop A cyclic PLC task with a 10 ms interval Calls the same controller instance once each cycle.

A function block preserves instance state between executions, which is why it matches the C++ object. Here state is exposed as an output for observation, like Controller::state(); callers should not write it. This scan-to-scan memory does not imply power-loss retention. See the vendor documentation for function blocks.

Signals and physical I/O

Input Current simulator Physical interpretation
entrySensor Box is within 0–0.10 m and has not entered Lane B Box detected at conveyor entry.
sortingSensor Box is within 1.95–2.05 m and has not entered Lane B Box detected near the sorting station.
laneBSensor Box has entered Lane B at 2.5 m Arrival confirmation at Lane B.
emergencyStop Boolean input, normally false Logical stop-active status: TRUE requests FAULT.
motorFault Boolean input, normally false Logical drive/starter fault status: TRUE requests FAULT.

These are logical signal meanings, not electrical wiring polarities. Hardware I/O mapping must provide those meanings to the controller. The C++ code treats safety signals as scan-level inputs; this ST translation has the same scope and is not a safety-rated emergency-stop implementation.

The ST controller does not know the box ID, conveyor speed, meters, or travel time. Those belong to the existing C++ plant or to the physical machine. Lane B selection is fixed; no route lookup is needed. All signals are level-sensitive: there are no edge detectors, timers, or debounce logic.

One cyclic execution

The C++ loop initializes sensors from the starting position, then repeats:

  1. Pass the current Inputs snapshot to controller.scan(inputs).
  2. Check the two safety inputs and update the sequence state.
  3. Calculate Outputs from the resulting state.
  4. Apply the outputs to the simulated plant and advance position by 10 ms.
  5. Recalculate sensors from position for the next scan.

On a PLC, the physical machine moves independently. The cyclic program reads mapped inputs, calls controller(inputs := inputs), and copies controller.outputs to mapped outputs. A common runtime model samples inputs at task start and transfers outputs to the I/O driver at task end; physical bus timing depends on the target configuration. See I/O task timing and cyclic task configuration. There is no sleep or infinite loop inside the ST program: the task schedules it.

Exact sequence semantics

Before CASE, either safety input forces FAULT, including when the previous state was COMPLETE. Otherwise the following sequence applies:

State before sequence Condition State after sequence
IDLE entrySensor TRANSPORTING
TRANSPORTING sortingSensor SORTING
SORTING laneBSensor COMPLETE
Any state No applicable condition Unchanged

There is no fall-through or repeated state evaluation. For example, if all three sensors are already TRUE at startup, three calls are required to reach COMPLETE. ST uses a CASE statement with the same branch ordering as the C++ switch.

Outputs are calculated after that transition, within the same invocation:

Resulting state Motor Diverter A Diverter B Diverter C
IDLE OFF OFF OFF OFF
TRANSPORTING ON OFF OFF OFF
SORTING ON OFF ON OFF
COMPLETE OFF OFF OFF OFF
FAULT OFF OFF OFF OFF

The motor remains on during sorting. Arrival feedback, not diverter activation, causes completion. COMPLETE has no normal exit; a safety fault can still move it to FAULT. FAULT stays latched when inputs clear. Neither version has a reset input. A newly initialized controller begins at IDLE; actual PLC restart/initialization behavior depends on the runtime and its retention settings.

Using the ST example

plc/FactoryFlow.st is readable source, not a vendor-specific project or a configured hardware deployment. In a PLC editor:

  1. Create the three data types, the FB_Controller function block, and the PLC_PRG program from the corresponding sections. Some editors require separate objects and separate declaration/body panes rather than a file import.
  2. Assign PLC_PRG to one cyclic task with a 10 ms interval.
  3. Bind PLC_PRG.inputs members to logical input channels and PLC_PRG.outputs members to output channels using the target's I/O mapping. No device addresses are prescribed here. Without mapping or manually supplied inputs, the default inputs remain FALSE and the controller stays IDLE.
  4. Keep the same controller instance between scans and call it once per cycle.

The source uses ordinary structs, an enum, IF, and CASE; it needs no libraries. The task and I/O setup belong to the chosen PLC tool, so they are described here rather than adding a vendor project to this milestone.

Checking equivalence

Both implementations use the same initialized state, safety priority, three conditional transitions, and four output assignments. To compare them in a PLC watch window, initialize a fresh instance for each scenario:

Scenario Inputs supplied on successive calls Expected result
Waiting All FALSE IDLE; all outputs OFF.
Normal flow Entry TRUE; sorting TRUE; Lane B TRUE TRANSPORTING, SORTING, COMPLETE; outputs as above.
No arrival yet Reach SORTING, then all sensors FALSE Remain SORTING with motor and B ON.
Simultaneous sensors All three sensors TRUE for three calls TRANSPORTING, then SORTING, then COMPLETE.
Emergency stop Set emergencyStop TRUE in any state FAULT; all outputs OFF in that call.
Motor fault Set motorFault TRUE in any state FAULT; all outputs OFF in that call.
Fault clears Enter FAULT, then clear both fault inputs Remain FAULT; all outputs OFF.

This translation has been reviewed against the C++ source. No ST compiler or PLC runtime is configured in this repository, so CMake/CTest validate only the C++ implementation and simulator, not ST compilation or execution.