RMI Protocol

A † marks information that comes from the official ComfoControl app (what it reads, writes or names), but that has not been checked on a unit.

Nodes

A RMI message is send towards a Node. The node ids are not fixed: the bridge announces the nodes that are available with CnNodeNotification messages when a session starts, and the ventilation unit is the node whose productId is 1 (ComfoAirQ) or 8 (ComfoAir Flex). On a ComfoAirQ with a ComfoConnect LAN C, this typically results in:

Node Description
0x01 The Ventilation Unit itself
0x30 The ComfoConnect LAN C device

On other setups the ids differ. A ComfoAir Flex has for example been seen at node 0x2D (45), with its connection board at node 0x29 (41).

Units

The Ventilation Unit is seperated into multiple Units, and sometimes even SubUnits. Here is a list of some existing units:

ID # of SubUnits Name Responsible for
0x01 1 NODE Represents the general node with attributes like serial nr, etc.
0x02 1 COMFOBUS Unit responsible for comfobus-communication. Probably stores the ID's of connected devices.
0x03 1 ERROR Stores errors, allows errors to be reset
0x15 10 SCHEDULE Responsible for managing Timers, the schedule, etc. Check here for level, bypass etc.
0x16 2 VALVE The valves: 01 extract (V11), 02 bypass/preheater (V21) †
0x17 2 FAN Represents the two fans: 01 exhaust (F12), 02 supply (F22) †
0x18 1 POWERSENSOR Counts the actual wattage of ventilation and accumulates to year and since factory reset
0x19 1 PREHEATER Represents the optional preheater
0x1A 1 HMI Represents the Display + Buttons
0x1B 1 RFCOMMUNICATION Wireless-communication with attached devices
0x1C 1 FILTER Counts the days since last filter change
0x1D 1 TEMPHUMCONTROL Controls the target temperature, if its cooling or heating period and some settings
0x1E 1 VENTILATIONCONFIG Responsible for managing various configuration options of the ventilation
0x20 1 NODECONFIGURATION Manages also some options
0x21 6 TEMPERATURESENSOR Represents the 6 temperature sensors in the ventilation (see below)
0x22 6 HUMIDITYSENSOR Represents the 6 humidity sensors (see below)
0x23 2 PRESSURESENSOR Represents both pressure sensors: 01 exhaust (P12), 02 supply (P22) †
0x24 1 PERIPHERALS Stores the ID of the ComfoCool attached, can reset peripheral errors here
0x25 4 ANALOGINPUT Provides data and functionality for the analog inputs, also the scaling for the voltages. Subunit 00 holds the settings the inputs share †
0x26 1 COOKERHOOD "Dummy" unit, probably represents the ComfoHood if attached
0x27 1 POSTHEATER Represents the optional post heater attached (temperature sens, config)
0x28 1 COMFOFOND "Dummy" unit, represents the optional comfofond
0x29 1 ERRORLOGGING The error log: the number of entries and the entries themselves †
0x2A 1 COMPONENTCHECK The component check of the service menu (fan, bypass, preheater, …) †
0x2B 8 CO2SENSOR The CO2 control, one subunit per zone (01-08); subunit 00 holds the shared settings †
0x2C 1 SERVICEPRINT Countries and article numbers, for installing the unit as another article †

The subunits of the sensor units are the same for temperature (T) and humidity (H) †:

SubUnit Sensor
0x01 Room (T10, H10)
0x02 Extract air (T11, H11)
0x03 Exhaust air (T12, H12)
0x04 Outdoor air (T20, H20)
0x05 Outdoor air after the preheater (T21, H21)
0x06 Supply air (T22, H22)

Their PDOs follow the same order: 272 + subunit for the temperatures and 288 + subunit for the humidities (see PROTOCOL-PDO.md).

Units of other nodes †

Other nodes reuse the unit ids from 0x15 on for their own units (like the ComfoClime below). The app knows these:

Node (productId) Unit Name
ComfoCool (6) 0x15 The cooler
ComfoCool (6) 0x16 Temperature sensors: 01 room (T10), 02 condensor (T13), 03 supply air (T23)
Option Box (4) 0x15 Inputs and outputs
ComfoAir Flex connection board (9) 0x15 Inputs and outputs
ComfoAir Flex connection board (9) 0x16 Node configuration
ComfoAir Flex connection board (9) 0x17 WiFi
CO2 sensor (10) 0x15 CO2 sensor; property 03 (BOOL, rw) enables it
CO2 sensor (10) 0x16 Temperature sensor; property 03 (BOOL, rw) enables it
CO2 sensor (10) 0x17 Humidity sensor; property 03 (BOOL, rw) enables it
CO2 sensor (10) 0x18 Ambient pressure sensor; property 03 (BOOL, rw) enables it
CO2 sensor (10) 0x19 Display: property 02 (UINT8, rw) is the LED mode (0=off, 1=warning only, 2=low, 3=medium, 4=high, 5=highest)

A CO2 sensor also has a property 0E (BOOL, rw) on its NODE unit, which the app calls the sensor mode.

Error codes

If an error occurs the reason can be one of the following:

Number Description
11 Unknown command: the unit has no such command
12 Unknown unit
13 Unknown subunit: higher than the number of subunits, or the command isn't allowed on this subunit
14 Unknown property
15 A range or step size was asked for a type that has none (BOOL, STRING, VERSION)
30 Value not in range (on a set; the step size isn't checked), or an invalid argument for a command
32 The property can't be read (get) or written (set)
40 The reply doesn't fit
41 The request is too short, e.g. a missing property id, value or argument
45 The node didn't answer within 1 second (set by the bridge)
52 The bridge is still busy with another RMI to that node (set by the bridge)

General commands

There are three commands which always exist on a given Unit:

  • 0x01: Get a single property

    This command reads a single property identified by the Unit, SubUnit and Property.

    Syntax: 01 Unit SubUnit Type Property

    The Type can be one of the following:

    • 0x00: None
    • 0x10: Actual value
    • 0x20: Range
    • 0x40: Step size

    Each writable property may have a range & step size. You can get those values by using the 0x20 and 0x40 Type values. You can request multiple types at the same time by OR'ing the value.

    Example: Request: 01 1d 01 70 03, Response: a0 00 96 00 90 01 0a 00 This gets the actual value, the range and the step size of the RMOT cooling threshold (an INT16) at once: 160 (16.0 °C), range 150 - 400, step 10.

    Reading the range and the step size together with the value costs no extra request.

    Example: Request: 01 20 01 10 03, Response: 34 32 31 30 00 (4210\0) This gets the maintainer password. Unit is NODECONFIGURATION, SubUnit is 01, get the actual value, Property 03.

  • 0x02: Get multiple properties

    This command allows to read multiple properties in one request.

    Syntax: 02 Count Unit SubUnit Type Property1 Property2 ... PropertyN [Unit SubUnit Type Property1 ...]

    Count is the number of Unit/SubUnit groups that follow, so one request can read properties from several units at once. In each group, the Type value needs to be OR'ed with the number of properties of that group. So if you want to read the actual value of 5 properties, the Type value needs to be 0x10 | 0x05 = 0x15. The official app puts at most 7 properties in a group. The response holds the values one after the other, in the order of the request.

    This document used to give the syntax as 02 Unit SubUnit 01 Type .... That reads the same bytes for the example below, because it reads one group (Count = 01) from Unit 01, SubUnit 01, but not for other units. Checked on a unit with TEMPHUMCONTROL (0x1D), SubUnit 01, properties 0x0A and 0x0B: the syntax above, 02 01 1D 01 12 0A 0B, replied e6 00 d2 00 (230 and 210, the same as two single reads), while the old syntax, 02 1D 01 01 12 0A 0B, got an RMI error.

    Reading several groups in one request was also checked on a unit: 02 02 1D 01 13 0A 08 02 01 01 12 14 06 reads TEMPHUMCONTROL properties 0x0A (INT16, the warm profile temperature), 0x08 (UINT8, the temperature profile mode) and 0x02 (INT16, the RMOT heating threshold), then NODE properties 0x14 (the name, a string ending with 00) and 0x06 (the firmware version, 4 bytes). The reply held the five values back to back in that order, the same as five single reads.

    Example: Request: 02 01 01 01 15 03 04 06 05 14, Response: \02 BEA000000000000\00 \00\10\10\c0 \02 ComfoAirQ\00 This reads the following property values of the NODE unit (the same ones the official app reads to identify a node):

    • 0x03: Product variant (02 is a ComfoAir Q450, seen on a unit)
    • 0x04: Serial Number
    • 0x06: Firmware version
    • 0x05: Hardware version †
    • 0x14: Ventilation Unit Name
  • 0x03: Set a single property

    This commands sets one property to the given value. The value needs to be in the range as identified within 0x01, otherwise an error of 30 is returned. The step size, however, is not checked.

    Syntax: 03 Unit SubUnit Property Value

    Example: 03 1D 01 04 00 Unit is TEMPHUMCONTROL, SubUnit 01, Property: 04, value 00 Sets the Property "Sensor ventilation: Temperature passive" to off

Property 0x01 of every unit is the zone of the node (UINT8, rw) †. It is a bit set: zone 1 is 01, zone 2 is 02, zone 3 is 04, and so on up to zone 8 (80); the ComfoConnect LAN C reports ff (every zone). That is why so many units answer 01 for property 0x01 in the tables below.

All other commands are >= 0x80 and dependent on the SubUnit. Please do not try to run command 0x80, 0x82 on NODECONFIGURATION (0x20), they will probably break your configuration, and even worse would be calling ANY >= 0x80 command on NODE (0x01). It can probably completely brick your ventilation. (It enters factory mode or tries to perform an update.)

Known properties for Node 0x01 (Ventilation Unit)

Where this table had no access or format, or one that differs from the official app, the Access and Format columns now follow the app †.

Unit SubUnit Property Access Format Description
NODE 0x01 0x01 rw UINT8 Zone (bit set, see above) †; 01 = 1
NODE 0x01 0x02 ro UINT8 Product id (01 = 1, ComfoAir Q) †
NODE 0x01 0x03 ro UINT8 Product variant: ComfoAir Q 1=Q350, 2=Q450 (seen on a unit), 3=Q600 †; ComfoAir Flex 1=250 (85 W), 2=350 (115 W), 3=350 (85 W). 02 = 2
NODE 0x01 0x04 ro STRING Serial number (BEA009999999999)
NODE 0x01 0x05 ro UINT8 Hardware version (02 = 2, seen on a unit)
NODE 0x01 0x06 ro UINT32 Firmware version (See version_decode())
NODE 0x01 0x07 ro UINT32 Version of the object definitions, encoded like the firmware version † (00541040)
NODE 0x01 0x08 ro STRING Model number (ComfoAir Q450 B R RF ST Quality)
NODE 0x01 0x09 ro UINT32 Version of the configuration data, encoded like the firmware version † (04000000)
NODE 0x01 0x0A ro UINT32 Version of the language data, encoded like the firmware version † (0004f0c0)
NODE 0x01 0x0B ro STRING Article number (471502004)
NODE 0x01 0x0C ro STRING Product serial number † (NULL)
NODE 0x01 0x0D ro STRING Current Country (BE)
NODE 0x01 0x14 rw STRING Ventilation Unit Name (ComfoAirQ); writable according to the app †
FILTER 0x01 0x02 rw UINT16 Filter warning period in days (21); a UINT16 in the app †
FILTER 0x01 0x03 rw UINT16 Filter lifetime in days (150); the app only uses it from firmware R1.9.0 on †
TEMPHUMCONTROL 0x01 0x01 rw UINT8 Zone † (01 = 1)
TEMPHUMCONTROL 0x01 0x02 rw INT16 RMOT for heating period (180 -> 18°C)
TEMPHUMCONTROL 0x01 0x03 rw INT16 RMOT for cooling period (200 -> 20°C)
TEMPHUMCONTROL 0x01 0x04 rw UINT8 Passive temperature control (0=off, 1=autoonly, 2=on)
TEMPHUMCONTROL 0x01 0x05 rw UINT8 Active temperature control (0=off, 1=autoonly, 2=on) † (00 = 0)
TEMPHUMCONTROL 0x01 0x06 rw UINT8 Humidity comfort control (o=off, 1=autoonly, 2=on)
TEMPHUMCONTROL 0x01 0x07 rw UINT8 Humidity protection (0=off, 1=autoonly, 2=on)
TEMPHUMCONTROL 0x01 0x08 rw UINT8 Temperature profile mode (0=adaptive, 1=fixed; a ComfoAir Q reports a range of 0-1)
TEMPHUMCONTROL 0x01 0x0A rw INT16 Target temperature for profile: Heating (230 -> 23°C)
TEMPHUMCONTROL 0x01 0x0B rw INT16 Target temperature for profile: Normal (210 -> 21°C)
TEMPHUMCONTROL 0x01 0x0C rw INT16 Target temperature for profile: Cooling (190 -> 19°C)
TEMPHUMCONTROL 0x01 0x0D rw UINT8 Temperature unit (0=Celsius, 1=Fahrenheit) † (00 = 0)
TEMPHUMCONTROL 0x01 0x0E rw UINT8 Speed of the passive temperature control (0=slow, 1=medium, 2=fast), from firmware R1.9.0 on †
VENTILATIONCONFIG 0x01 0x01 rw UINT8 Zone † (01 = 1)
VENTILATIONCONFIG 0x01 0x02 ro UINT8 Flags of the allowed presets † (0f = 15)
VENTILATIONCONFIG 0x01 0x03 rw INT16 Ventilation speed in "Away" Level (75); a UINT16 in the app †
VENTILATIONCONFIG 0x01 0x04 rw INT16 Ventilation speed in "Low" Level (110); a UINT16 in the app †
VENTILATIONCONFIG 0x01 0x05 rw INT16 Ventilation speed in "Medium" Level (180); a UINT16 in the app †
VENTILATIONCONFIG 0x01 0x06 rw INT16 Ventilation speed in "High" Level (370); a UINT16 in the app †
VENTILATIONCONFIG 0x01 0x07 rw UINT8 Height above sea level (0=0-500, 1=500-1000, 2=1000-1500, 3=1500-2000)
VENTILATIONCONFIG 0x01 0x08 ro UINT16 Measured maximum flow † (8b01 = 395)
VENTILATIONCONFIG 0x01 0x09 rw UINT8 Ventilation control mode (0=flow control, 1=constant flow)
VENTILATIONCONFIG 0x01 0x0A rw INT16 Unbalance in direct fan control (DFC) mode, in 0.1 % † (ecff = -20 -> -2.0 %)
VENTILATIONCONFIG 0x01 0x0B rw UINT16 Bathroom switch, activation delay (300 = 300 sec)
VENTILATIONCONFIG 0x01 0x0C rw UINT8 Bathroom switch, deactivation delay (30 = 30 min)
VENTILATIONCONFIG 0x01 0x0D rw UINT8 Bathroom switch, mode (0=fixed, 1=mirrored)
VENTILATIONCONFIG 0x01 0x0E rw UINT8 Airflow unit (1=kg/h, 2=l/s, 3=m³/h) † (03 = 3)
VENTILATIONCONFIG 0x01 0x0F rw BOOL Direct fan control (DFC) enabled † (00 = 0)
VENTILATIONCONFIG 0x01 0x11 rw UINT16 Flow in direct fan control (DFC) mode † (c800 = 200)
VENTILATIONCONFIG 0x01 0x12 rw INT16 Unbalance (9dff = -99 -> -9.9 %)
VENTILATIONCONFIG 0x01 0x13 ro UINT16 Maximum reference flow, exhaust fan † (0000 = 0)
VENTILATIONCONFIG 0x01 0x14 ro UINT16 Maximum reference flow, supply fan † (0000 = 0)
VENTILATIONCONFIG 0x01 0x15 ro UINT16 Maximum reference fan speed, exhaust fan † (980d = 3480)
VENTILATIONCONFIG 0x01 0x16 ro UINT16 Maximum reference fan speed, supply fan † (660c = 3174)
VENTILATIONCONFIG 0x01 0x17 ro UINT16 Medium reference flow, exhaust fan † (0000 = 0)
VENTILATIONCONFIG 0x01 0x18 ro UINT16 Medium reference flow, supply fan † (0000 = 0)
VENTILATIONCONFIG 0x01 0x19 ro UINT16 Medium reference fan speed, exhaust fan † (8107 = 1921)
VENTILATIONCONFIG 0x01 0x1A ro UINT16 Medium reference fan speed, supply fan † (a106 = 1697)
VENTILATIONCONFIG 0x01 0x1B ro UINT16 Fan speed at maximum pressure, exhaust fan † (0f05 = 1295)
VENTILATIONCONFIG 0x01 0x1C ro UINT16 Fan speed at maximum pressure, supply fan † (0c05 = 1292)
VENTILATIONCONFIG 0x01 0x1D ro UINT16 Expected fan speed without pressure, exhaust fan † (5304 = 1107)
VENTILATIONCONFIG 0x01 0x1E ro UINT16 Expected fan speed without pressure, supply fan † (1304 = 1043)
VENTILATIONCONFIG 0x01 0x1F ro UINT16 Expected maximum flow †
VENTILATIONCONFIG 0x01 0x20 rw UINT8 ComfoHood switch-off delay, from firmware R1.5.0 on †
NODECONFIGURATION 0x01 0x01 rw UINT8 Zone † (01 = 1)
NODECONFIGURATION 0x01 0x03 ro STRING Maintainer password (NL=4210, BE=2468, DE=4210); 4 characters †
NODECONFIGURATION 0x01 0x04 ro BOOL ComfoSense allowed †. This table listed the orientation here before; the app reads it from 0x06
NODECONFIGURATION 0x01 0x05 ro BOOL ComfoSwitch allowed † (01 = 1)
NODECONFIGURATION 0x01 0x06 rw UINT8 Orientation (0=left, 1=right) † (00 = 0)
NODECONFIGURATION 0x01 0x07 rw UINT8 Position of the condensation drain (0=none, 1=left, 2=right) † (00 = 0)
NODECONFIGURATION 0x01 0x08 rw BOOL Fireplace present † (01 = 1)
NODECONFIGURATION 0x01 0x0A rw UINT8 User level of the menu (0=basic, 1=advanced, 2=installer) † (00 = 0)
NODECONFIGURATION 0x01 0x0B rw UINT8 Preset used to fine tune the airflow (0=away, 1=low, 2=medium, 3=high) † (02 = 2)
NODECONFIGURATION 0x01 0x0C rw BOOL Commissioning finished † (01 = 1)
NODECONFIGURATION 0x01 0x0D rw UINT8 Heat recovery type (0=HRV, 1=ERV), from firmware R1.5.0 on †

Other properties of the ventilation unit †

The app also reads and writes these properties. None of them were checked on a unit.

Unit SubUnit Property Access Format Description
COMFOBUS 0x01 0x02 ro BOOL The CAN bus is off
COMFOBUS 0x01 0x03 ro UINT8 CAN receive error counter
COMFOBUS 0x01 0x04 ro UINT8 CAN transmit error counter
VALVE 0x01-0x02 0x02 rw UINT16 Valve position, in 0.1 %
FAN 0x01-0x02 0x02 ro BOOL The fan may be disabled
PREHEATER 0x01 0x02 ro BOOL Preheater present
PREHEATER 0x01 0x03 ro UINT8 Location of the preheater (0=left, 1=right)
PREHEATER 0x01 0x04 rw UINT8 Duty cycle, in %
PREHEATER 0x01 0x05 rw UINT8 Ratio, in %
HMI 0x01 0x02 ro BOOL Display present
HMI 0x01 0x03 rw UINT8 Brightness
HMI 0x01 0x04 rw STRING Language
HMI 0x01 0x05 rw BOOL Child lock
HMI 0x01 0x06 rw UINT8 Door state (also PDO 162)
HMI 0x01 0x07 rw UINT8 Button states (also PDO 161)
HMI 0x01 0x08 ro BOOL LCD operational (also PDO 160)
RFCOMMUNICATION 0x01 0x02 ro BOOL RF present
RFCOMMUNICATION 0x01 0x03 ro BOOL RF enabled
RFCOMMUNICATION 0x01 0x04 rw UINT8 Priority of RF sensors (0=on, 1=autoonly, 2=off)
RFCOMMUNICATION 0x01 0x05 rw UINT8 Function of RF sensors (0=flow proportional, 1=flow preset)
RFCOMMUNICATION 0x01 0x06 rw UINT8 RF duty, in %
TEMPERATURESENSOR 0x01-0x06 0x02 ro BOOL Sensor present
HUMIDITYSENSOR 0x01-0x06 0x02 ro BOOL Sensor present
PRESSURESENSOR 0x01-0x02 0x02 ro BOOL Sensor present
PERIPHERALS 0x01 0x0B ro UINT8 The ComfoCool that is attached
ANALOGINPUT 0x00 0x01 rw UINT8 Priority of the analog inputs (0=on, 1=autoonly, 2=off)
ANALOGINPUT 0x00 0x02 rw UINT8 Function of the analog inputs (0=flow proportional, 1=flow preset)
ANALOGINPUT 0x00 0x03 ro BOOL Analog inputs present
ANALOGINPUT 0x01-0x04 0x02 rw UINT8 Level for 0 %
ANALOGINPUT 0x01-0x04 0x03 rw UINT8 Level for 100 %
ANALOGINPUT 0x01-0x04 0x04 rw UINT8 Mode (0=steer, 1=control)
ANALOGINPUT 0x01-0x04 0x05 rw UINT8 Setpoint in control mode
ANALOGINPUT 0x01-0x04 0x06 rw UINT8 Proportional band in control mode, in % (0-255)
ANALOGINPUT 0x01-0x04 0x07 rw UINT16 Integral time in control mode
ANALOGINPUT 0x01-0x04 0x08 rw BOOL Input enabled
POSTHEATER 0x01 0x03 rw INT16 Proportional band
POSTHEATER 0x01 0x04 rw UINT16 Integral time
POSTHEATER 0x01 0x05 rw INT16 Comfort temperature, in 0.1 °C
CO2SENSOR 0x00 0x01 rw UINT8 Priority of the CO2 control (0=on, 1=autoonly, 2=off)
CO2SENSOR 0x00 0x02 rw UINT8 Function of the CO2 control (0=flow proportional, 1=flow preset)
CO2SENSOR 0x01-0x08 0x02 rw UINT16 Level for 0 %
CO2SENSOR 0x01-0x08 0x03 rw UINT16 Level for 100 %
CO2SENSOR 0x01-0x08 0x05 rw UINT16 Setpoint in control mode
CO2SENSOR 0x01-0x08 0x06 rw UINT8 Proportional band in control mode, in % (0-250)
CO2SENSOR 0x01-0x08 0x07 rw UINT16 Integral time in control mode
CO2SENSOR 0x01-0x08 0x08 rw BOOL CO2 control of the zone enabled

On subunit 00 of ANALOGINPUT and CO2SENSOR, the app reads property 0x01 as the priority, not as the zone.

Known properties for Node 0x30 (ComfoConnect LAN C)

Unit SubUnit Property Access Format Description
NODE 0x01 0x01 rw UINT8 Zone † (ff = 255, every zone)
NODE 0x01 0x02 ro UINT8 Product id † (05 = 5, Zehnder gateway)
NODE 0x01 0x03 ro UINT8 Product variant † (00 = 0)
NODE 0x01 0x04 ro STRING Serial number (DEM0999999999)
NODE 0x01 0x05 ro UINT8 Hardware version † (01 = 1)
NODE 0x01 0x06 ro UINT32 Firmware version (See version_decode())
NODE 0x01 0x07 ro UINT32 Version of the object definitions, encoded like the firmware version † (008c10c0)
NODE 0x01 0x14 rw STRING Unit Name (ComfoConnect LAN C)

Known properties for a ComfoClime node (productId 0x14)

The ComfoClime reuses unit ids 0x16 and 0x17 for its own purposes, so these are not the VALVE and FAN units of a ventilation unit. Reverse engineered from the ComfoClime's own HTTP API, which addresses these as unit/subunit/property. All temperatures are stored in tenths of a degree.

Unit SubUnit Property Access Format Description
NODE 0x01 0x04 ro STRING Serial number (MBE0999999999)
NODE 0x01 0x06 ro UINT32 Firmware version (See version_decode())
NODE 0x01 0x14 rw STRING Unit Name
CLIME_TEMPCONFIG 0x01 0x02 rw UINT8 Automatic season detection (0=off, 1=on)
CLIME_TEMPCONFIG 0x01 0x03 rw UINT8 Season (0=transition, 1=heating, 2=cooling)
CLIME_TEMPCONFIG 0x01 0x04 rw INT16 Heating curve knee point (5.0 - 15.0 °C)
CLIME_TEMPCONFIG 0x01 0x05 rw INT16 Cooling curve knee point (15.0 - 25.0 °C)
CLIME_TEMPCONFIG 0x01 0x09 rw INT16 Heating comfort temperature (15.0 - 25.0 °C)
CLIME_TEMPCONFIG 0x01 0x0A rw INT16 Cooling comfort temperature (20.0 - 28.0 °C)
CLIME_TEMPCONFIG 0x01 0x0B rw INT16 Maximum temperature while cooling (20.0 - 28.0 °C)
CLIME_TEMPCONFIG 0x01 0x0C rw INT16 Heating reduction delta (0.0 - 5.0 °C)
CLIME_TEMPCONFIG 0x01 0x0D rw INT16 Manual target temperature (18.0 - 28.0 °C)
CLIME_TEMPCONFIG 0x01 0x15 rw UINT8 Heat pump standby (0=active, 1=standby)
CLIME_TEMPCONFIG 0x01 0x1D rw UINT8 Temperature profile (0=comfort, 1=power, 2=eco)
CLIME_HEATPUMP 0x01 0x03 rw INT16 Heat pump maximum temperature (40.0 - 60.0 °C)
CLIME_HEATPUMP 0x01 0x04 rw INT16 Heat pump minimum temperature (10.0 - 17.0 °C)

The ComfoClime also drives two properties on the ventilation unit node:

Unit SubUnit Property Access Format Description
TEMPHUMCONTROL 0x01 0x02 rw INT16 RMOT heating threshold (5.0 - 20.0 °C)
TEMPHUMCONTROL 0x01 0x03 rw INT16 RMOT cooling threshold (5.0 - 35.0 °C)

SCHEDULE Unit commands

  • 0x80: GETSCHEDULEENTRY
  • 0x81: ENABLESCHEDULEENTRY
  • 0x82: DISABLESCHEDULEENTRY
  • 0x83: GETTIMERENTRY
  • 0x84: ENABLETIMERENTRY
  • 0x85: DISABLETIMERENTRY
  • 0x86: GETSCHEDULE
  • 0x87: GETTIMERS

Known schedules

Each subunit has one or more timers that override a setting. The request is command subunit timer:

  • 0x83 subunit timer: get the timer. Reply: active(u8) delay(i32) duration(i32) remaining(i32) value(u8). An inactive timer keeps the fields of its last run, so only use them when active is 01.
  • 0x84 subunit timer delay(i32) duration(i32) value(u8): start the timer. A duration of -1 runs until it is cancelled. A duration of 1 lets the unit pick its default (the speed and manual mode timers use this, like the official app).
  • 0x85 subunit timer: cancel the timer. The official app cancels all timers of a subunit at once with timer 00 †.
  • 0x87 subunit: get all timers of the subunit †. Reply: one byte, then the 14 bytes of the 0x83 reply for every timer of the subunit, from timer 1 on.

The constants are in aiocomfoconnect/const.py, and ComfoConnect has get_timer, set_timer and cancel_timer.

SubUnit Timer Constants Description
0x01 0x01 SCHEDULE_PRESET, TIMER_DEFAULT Fan speed (00=away/01=low/02=medium/03=high)
0x01 0x02 PRESETRF
0x01 0x03 PRESETANALOG
0x01 0x04 PRESETRFANALOG
0x01 0x05 MANUALMODE
0x01 0x06 SCHEDULE_PRESET, TIMER_BOOST Boost (03=high)
0x01 0x07 BOOSTRF
0x01 0x08 BOOSTSWITCH
0x01 0x0b SCHEDULE_PRESET, TIMER_AWAY Away (00=away)
0x02 0x01 SCHEDULE_BYPASS, TIMER_DEFAULT Bypass (01=on/02=off, no timer is auto)
0x03 0x01 SCHEDULE_TEMPERATURE_PROFILE, TIMER_DEFAULT Temperature profile (00=normal/01=cool/02=warm)
0x04 0x01 Standby (00=off/01=on) †
0x05 0x01 SCHEDULE_COMFOCOOL, TIMER_DEFAULT ComfoCool (00=auto/01=off in the official app)
0x06 0x01 SCHEDULE_SUPPLY_ONLY, TIMER_DEFAULT Exhaust fan off (01), so supply only
0x07 0x01 SCHEDULE_EXHAUST_ONLY, TIMER_DEFAULT Supply fan off (01), so exhaust only
0x08 0x01 SCHEDULE_MANUAL_MODE, TIMER_DEFAULT Manual mode (01=manual, no timer is auto)
0x09 0x01 ComfoHood (00=off/01=on) †
0x09 0x02 ComfoHood switch timer (00=off/01=on) †
0x0a 0x01 Postheater (00=off/01=heat/02=comfort) †

The durations the official app offers for a timer are 1, 2, 3, 6 and 12 hours and 1 day; for the ComfoCool and for supply fan off (exhaust only) also "continuous", a duration of -1 †.

Week schedule †

Next to the timers, every subunit has a week schedule of 10 entries. The official app reads and writes it like this:

  • 0x86 subunit: get the whole schedule. Reply: 130 bytes, 13 bytes for each of the 10 entries.
  • 0x80 subunit entry: get one entry. Reply: the 13 bytes of that entry.
  • 0x81 subunit entry day hour minute duration(i32) value(u8): enable an entry. The app leaves entry 00 alone and adds new entries in the first free slot from 01 to 09.
  • 0x82 subunit entry: disable an entry.

An entry is enabled(u8) day(u8) hour(u8) minute(u8) duration(i32) remaining(i32) value(u8): the entry starts at hour:minute, lasts duration seconds (the app adds a day when the end time is earlier than the start time) and sets the subunit to value, with the same values as the timers. When enabled is not 01 the rest of the entry has no meaning. The days are: 00=every day, 01=Monday to 07=Sunday, 08=weekdays, 09=weekend, 0a=no day.

The PDOs with base 32 and 320 report the active entry and the enabled entries (see Schedule PDOs).

ERROR Unit commands

These commands are sent to subunit 0x01, e.g. 80 03 01.

  • 0x80: GETACTIVEERRORS. The reply is a bit set of 32 bytes: bit n is set when error n is active.
  • 0x81 error: reset one error, given by its id (u8).
  • 0x82: RESETALLERRORS

After an error was reset, the node sends its alarm again.

Error list

Error ID Description
21 DANGER! OVERHEATING! Two or more sensors are detecting an incorrect temperature. Ventilation has stopped.
22 Temperature too high for ComfoAir Q (TEMP_HRU ERROR)
23 The extract air temperature sensor has a malfunction (SENSOR_ETA ERROR)
24 The extract air temperature sensor is detecting an incorrect temperature (TEMP_SENSOR_ETA ERROR)
25 The exhaust air temperature sensor has a malfunction (SENSOR_EHA ERROR)
26 The exhaust air temperature sensor is detecting an incorrect temperature (TEMP_SENSOR_EHA ERROR)
27 The outdoor air temperature sensor has a malfunction (SENSOR_ODA ERROR)
28 The outdoor air temperature sensor is detecting an incorrect temperature (TEMP_SENSOR_ODA ERROR)
29 The pre-conditioned outdoor air temperature sensor has a malfunction
30 The pre-conditioned outdoor air temperature sensor is detecting an incorrect temperature (TEMP_SENSOR_P-ODA ERROR)
31 The supply air temperature sensor has a malfunction (SENSOR_SUP ERROR)
32 The supply air temperature sensor is detecting an incorrect temperature (TEMP_SENSOR_SUP ERROR)
33 The Ventilation Unit has not been commissioned (INIT ERROR)
34 The front door is open
35 The Pre-heater is present, but not in the correct position (right/left). (PREHEAT_LOCATION ERROR)
37 The pre-heater has a malfunction (PREHEAT ERROR)
38 The pre-heater has a malfunction (PREHEAT ERROR)
39 The extract air humidity sensor has a malfunction (SENSOR_ETA ERROR)
41 The exhaust air humidity sensor has a malfunction (SENSOR_EHA ERROR)
43 The outdoor air humidity sensor has a malfunction (SENSOR_ODA ERROR)
45 The outdoor air humidity sensor has a malfunction (SENSOR_P-ODA ERROR)
47 The supply air humidity sensor has a malfunction (SENSOR_SUP ERROR)
49 The exhaust air flow sensor has a malfunction (SENSOR_EHA ERROR)
50 The supply air flow sensor has a malfunction (SENSOR_SUP ERROR)
51 The extract air fan has a malfunction (FAN_EHA ERROR)
52 The supply air fan has a malfunction (FAN_SUP ERROR)
53 Exhaust air pressure too high. Check air outlets, ducts and filters for pollution and obstructions. Check valve settings (EXT_PRESSURE_EHA ERROR)
54 Supply air pressure too high. Check air outlets, ducts and filters for pollution and obstructions. Check valve settings. (EXT_PRESSURE_SUP ERROR)
55 The extract air fan has a malfunction (FAN_EHA ERROR)
56 The supply air fan has a malfunction (FAN_SUP ERROR)
57 The exhaust air flow is not reaching its set point (AIRFLOW_EHA ERROR)
58 The supply air flow is not reaching its set point (AIRFLOW_SUP ERROR)
59 Failed to reach required temperature too often for outdoor air after pre-heater (TEMPCONTROL_P-ODA ERROR)
60 Failed to reach required temperature too often for supply air. The modulating by-pass may have a malfunction. (TEMPCONTROL_SUP ERROR)
61 Supply air temperature is too low too often (TEMP_SUP_MIN ERROR)
62 Unbalance occurred too often beyond tolerance levels in past period (UNBALANCE ERROR)
63 Postheater was present, but is no longer detected (POSTHEAT_CONNECT ERROR)
64 Temperature sensor value for supply air ComfoCool exceeded limit too often (CCOOL_TEMP ERROR)
65 Room temperature sensor was present, but is no longer detected (T_ROOM_PRES ERROR)
66 RF Communication hardware was present, but is no longer detected (RF_PRES ERROR)
67 Option Box was present, but is no longer detected (OPTION_BOX CONNECT ERROR)
68 Pre-heater was present, but is no longer detected (PREHEAT_PRES ERROR)
69 Postheater was present, but is no longer detected (POSTHEAT_CONNECT ERROR)
# Firmware 1.4.0+ (the official app uses this numbering for every version except exactly R1.4.0 †)
70 Analog input 1 was present, but is no longer detected (ANALOG_1_PRES ERROR)
71 Analog input 2 was present, but is no longer detected (ANALOG_2_PRES ERROR)
72 Analog input 3 was present, but is no longer detected (ANALOG_3_PRES ERROR)
73 Analog input 4 was present, but is no longer detected (ANALOG_4_PRES ERROR)
74 ComfoHood was present, but is no longer detected (HOOD_CONNECT ERROR)
75 ComfoCool was present, but is no longer detected (CCOOL_CONNECT ERROR)
76 ComfoFond was present, but is no longer detected (GROUND_HEAT_CONNECT ERROR)
77 The filters of the Ventilation Unit must be replaced now
78 It is necessary to replace or clean the external filter
79 Order new filters now, because the remaining filter life time is limited
80 Service mode is active (SERVICE MODE)
81 Preheater has no communication with the ComfoAir unit (PREHEAT ERROR , 1081)
82 ComfoHood temperature error (HOOD_TEMP ERROR)
83 Postheater temperature error (POSTHEAT_TEMP ERROR)
84 Outdoor temperature of ComfoFond error (GROUND_HEAT_TEMP ERROR)
85 Analog input 1 error (ANALOG_1_IN ERROR)
86 Analog input 2 error (ANALOG_2_IN ERROR)
87 Analog input 3 error (ANALOG_3_IN ERROR)
88 Analog input 4 error (ANALOG_4_IN ERROR)
89 Bypass is in manual mode
90 ComfoCool is overheating
91 ComfoCool compressor error (CCOOL_COMPRESSOR ERROR)
92 ComfoCool room temperature sensor error (CCOOL_TEMP ERROR)
93 ComfoCool condensor temperature sensor error (CCOOL_TEMP ERROR)
94 ComfoCool supply air temperature sensor error (CCOOL_TEMP ERROR)
95 ComfoHood temperature is too high (HOOD_TEMP ERROR)
96 ComfoHood is activated
97 UNKNOWN: QM_Constraint_min_ERR
98 UNKNOWN: H_21_qm_min_ERR
99 Configuration error
100 Error analysis is in progress…
101 ComfoNet Error
102 The number of CO2 sensors has decreased – one or more sensors are no longer detected
103 More than 8 sensors detected in a zone
104 CO₂ Sensor C error
105 General I²C bus error †
# Firmware 1.4.0 (the official app uses this numbering only for exactly R1.4.0 †)
70 ComfoHood was present, but is no longer detected (HOOD_CONNECT ERROR)
71 ComfoCool was present, but is no longer detected (CCOOL_CONNECT ERROR)
72 ComfoFond was present, but is no longer detected (GROUND_HEAT_CONNECT ERROR)
73 The filters of the Ventilation Unit must be replaced now
74 It is necessary to replace or clean the external filter
75 Order new filters now, because the remaining filter life time is limited
76 Service mode is active (SERVICE MODE)
77 Preheater has no communication with the ComfoAir unit (PREHEAT ERROR , 1081)
78 ComfoHood temperature error (HOOD_TEMP ERROR)
79 Postheater temperature error (POSTHEAT_TEMP ERROR)
80 Outdoor temperature of ComfoFond error (GROUND_HEAT_TEMP ERROR)
81 Bypass is in manual mode
82 ComfoCool is overheating
83 ComfoCool compressor error (CCOOL_COMPRESSOR ERROR)
84 ComfoCool room temperature sensor error (CCOOL_TEMP ERROR)
85 ComfoCool condensor temperature sensor error (CCOOL_TEMP ERROR)
86 ComfoCool supply air temperature sensor error (CCOOL_TEMP ERROR)

Commands of other units †

The official app uses these commands of the ventilation unit. Like the warning above says, some of them change the configuration or the state of the unit, so don't try them on a unit you care about.

Unit Command Arguments Description
NODE 0x80 Enter update mode
NODE 0x81 Enter factory mode
NODE 0x82 Enter operational mode
NODE 0x83 Enter service mode
NODECONFIGURATION 0x80 which (u8) Revert to defaults: 0=factory, 1=installer, 2=user without the schedules, 3=user with the schedules
NODECONFIGURATION 0x82 event (u8) Commissioning wizard: 0=abort, 1=finish, 2=stop and save, 3=start
FAN 0x81 one byte Enable the fan
FAN 0x82 Disable the fan
POWERSENSOR 0x80 Reset the analysis
PREHEATER 0x80 Reset the analysis
HMI 0x80 Get the languages
RFCOMMUNICATION 0x80 Start pairing an RF device (follow it with PDO 176)
RFCOMMUNICATION 0x81 Stop pairing
FILTER 0x80 Begin the filter replacement
FILTER 0x81 End the filter replacement
FILTER 0x82 Abort the filter replacement
FILTER 0x83 Reset the days left of the filter
VENTILATIONCONFIG 0x80 Set the airflow units
PERIPHERALS 0x80 Reset the presence of the peripherals
ERRORLOGGING 0x80 type (u8): 0=error, 1=assert Get the number of log entries
ERRORLOGGING 0x81 Get a log entry
COMPONENTCHECK 0x80 component (u8) Start the check of 0=none, 1=fan, 2=bypass, 3=preheater, 4=postheater, 5=ComfoFond, 6=ComfoCool
COMPONENTCHECK 0x81 Stop the check
COMPONENTCHECK 0x82 Reset the timer of the check
SERVICEPRINT 0x7e Get the number of countries
SERVICEPRINT 0x7f index (u8) Get the name of a country
SERVICEPRINT 0x80 country (string) Get the number of article numbers
SERVICEPRINT 0x81 country (string), index (u8) Get an article number
SERVICEPRINT 0x82 two strings Get the description of an article
SERVICEPRINT 0x83 two strings Install an article

Example list of commonly-used commands

See the comfoconnect.py file for more commands and how they are constructed.

Command Description
84 15 01 01 00000000 01000000 00 Switch to fan speed away
84 15 01 01 00000000 01000000 01 Switch to fan speed 1
84 15 01 01 00000000 01000000 02 Switch to fan speed 2
84 15 01 01 00000000 01000000 03 Switch to fan speed 3
84 15 01 06 00000000 58020000 03 Boost mode: start for 10m (= 600 seconds = 0x0258)
85 15 01 06 Boost mode: end
85 15 08 01 Switch to auto mode
84 15 08 01 00000000 01000000 01 Switch to manual mode
84 15 06 01 00000000 100e0000 01 Set ventilation mode: supply only for 1 hour
85 15 06 01 Set ventilation mode: balance mode
84 15 03 01 00000000 ffffffff 00 Set temperature profile: normal
84 15 03 01 00000000 ffffffff 01 Set temperature profile: cool
84 15 03 01 00000000 ffffffff 02 Set temperature profile: warm
84 15 02 01 00000000 100e0000 01 Set bypass: activated for 1 hour
84 15 02 01 00000000 100e0000 02 Set bypass: deactivated for 1 hour
85 15 02 01 Set bypass: auto
03 1d 01 04 00 Set sensor ventilation: temperature passive: off
03 1d 01 04 01 Set sensor ventilation: temperature passive: auto only
03 1d 01 04 02 Set sensor ventilation: temperature passive: on
03 1d 01 06 00 Set sensor ventilation: humidity comfort: off
03 1d 01 06 01 Set sensor ventilation: humidity comfort: auto only
03 1d 01 06 02 Set sensor ventilation: humidity comfort: on
03 1d 01 07 00 Set sensor ventilation: humidity protection: off
03 1d 01 07 01 Set sensor ventilation: humidity protection: auto
03 1d 01 07 02 Set sensor ventilation: humidity protection: on